Liquid Load Banks

Data Center Products

In the demanding world of data centers and High-Performance Computing (HPC), reliable infrastructure is non-negotiable. Thermon’s Poseidon™ Liquid Load Bank (for US markets) and Pontus™ Liquid Load Bank (for non-US markets) are engineered to provide precise, real-world thermal and electrical demand simulation. These mission-critical systems validate the performance of your essential data center components, ensuring everything operates flawlessly from day one.

Thermon’s liquid load banks offer a purpose-built solution for the rigorous demands of data center commissioning and validation. They are indispensable for testing critical HPC data center infrastructure, including:

  • Mechanical Cooling Equipment (i.e. Chillers, Cooling Towers, etc.)
  • Coolant Distribution Units (CDUs)
  • Uninterruptible Power Supplies (UPS)
  • Backup Power Generators

By accurately simulating real-world thermal and electrical demand, our liquid load banks empower you to confidently validate your systems, minimizing risks and maximizing uptime.

 

To meet global demand, Thermon’s Poseidon and Pontus Liquid Load Banks are designed to comply with regional certifications and standards, giving you peace of mind no matter where your operations are located.

  • For US Markets: Poseidon Liquid Load Bank meets stringent US standards and certifications, including ASME, NEC, ANSI, and UL. Poseidon incorporates standard systems and controls specifically tailored to the regulatory needs of the US market.
  • For Non-US Markets: Pontus Liquid Load Bank meets key international standards and certifications such as CRN, CE-mark, PED, and ASME. Pontus Liquid Load Banks can also be custom engineered to meet additional regional certification and standard requirements, ensuring seamless integration into any global operation.

FEATURES:

  • 10” Siemens SIMATIC Human Machine Interface (HMI) with simple and easy controls
  • Temperature, Pressure and Flow displayed on HMI
  • Compatible with all of the industry-leading providers of Coolant Distribution Units, Power Distribution Units and Chillers
  • Mushroom E-stop, pilot light, and on/offpower switch
  • Audible alarm system for high temperature,low flow, or low water conditions andalarm logging on the HMI
  • Heat duty regulation based Specific kWinput or percentage of available load (kW)
  • Equipped with quick connection camlockpower connectors rated for 400 amps (5per phase + 1 ground)
  • Stainless steel construction for all wettedparts in 304SS (upgrade optional to 316L)
  • Forklift pockets, top four corner liftingprovision, and heavy-duty casters
  • Integrated air vent and drain valve
  • Mechanical guarding around HMI panel,door operators, and inlet/outlet flangeconnection points
  • Protection for electrical camlockconnectors when not in use
  • Equipped with low profile butterfly valves(4” – 150# Flanged Connection) on inletand outlet nozzle
  • Rigid steel frame with extended handlesand grab bars
  • All external surfaces are powder-coated fordurability

RELIABILITY:

  • Step control and Silicon ControlledRectifier modulation control for heat dutyregulation to extend the life of heatingelements and contactors
  • Vessel insulation prevents over-radiationof heat to neighboring control enclosuresand touch surfaces to improve operatorsafety
  • 24 replaceable electric heater bundles tosupport easy maintenance
  • 100A rated fuse connections to mitigatefailure (considers 25% safety factor)
  • EMA 12 – IP54 rated electrical enclosurefor protection to external environment
  • Magnetic contactors rated for over 500kcycles
  • Global support from responsive Thermonengineering and site services teams

LIQUID LOAD BANKS: THERMON POSEIDON™ & THERMON PONTUS™

To meet global demand, Thermon’s Poseidon™ and Pontus™ Liquid Load Banks are designed to comply with regional certifications and standards, giving you peace of mind no matter where your operations are located.

Certification and Compliance

  • For US Markets: Poseidon™ Liquid Load Bank meets stringent US standards and certifications, including ASME, NEC, ANSI, and UL. Poseidon incorporates standard systems and controls specifically tailored to the regulatory needs of the US market.

 

  • For Non-US Markets: Pontus™ Liquid Load Bank meets key international standards and certifications such as CRN, CE-mark, PED, and ASME. Pontus Liquid Load Banks can also be custom engineered to meet additional regional certification and standard requirements, ensuring seamless integration into any global operation.

LIQUID LOAD BANKS: THERMON POSEIDON™ & THERMON PONTUS™

To meet global demand, Thermon’s Poseidon™ and Pontus™ Liquid Load Banks are designed to comply with regional certifications and standards, giving you peace of mind no matter where your operations are located.

Smaller Footprint

  • Compact design: 43”W x 72”L x 75”H
  • Weight (dry): 2,500 lbs. (1,134 kg)
  • Dedicated power cabinet with space-saving buss bar arrangement
  • Tighter element pitch and higher heat duties for maximum performance
  • Capacity rating up to 640kW at 480V (dual voltage rating down to 415V)
  • Designed for modular, mobile testing in HPC and data center environments

For more information contact us at 1-877-705-9864 or info@wtmi-usa.com